Series 65 Integrating Ionisation Smoke Detector

Series 65 Integrating Ionisation Smoke Detector

£30.87

Ionisation detectors use a low activity radioactive foil to detect fires by irradiating the air in the smoke chamber and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm. Circuitry in the Integrating Ionisation Smoke Detector protects against transient levels of smoke above the normal threshold for up to 20 seconds.

The detector has a moulded self-extinguishing white polycarbonate case with wind resistant smoke inlets. Nickel plated stainless steel wiper contacts connect the detector to the base.

Inside the detector case a printed circuit board has the ionisation chamber mounted on one side and the signal processing electronics on the other.

The ionisation chamber consists of a reference chamber contained inside a smoke chamber (Fig. 1). The outer smoke chamber has inlet apertures fitted with insect resistant mesh. The radioactive source holder and smoke chamber form positive and negative electrodes respectively.

An Americium 241 radioactive source mounted within the reference chamber irradiates the air in both chambers, producing positive and negative ions. A voltage across the electrodes produces an electric field. Ions are attracted to the electrode of the opposite sign to their own charge. Many recombine but a small electric current flows between the electrodes. At the junction between reference and smoke chambers the sensing electrode converts variations in chamber current into voltage changes.

When smoke particles enter the ionisation chamber ions become attached to them with the result that the current flowing through the chambers decreases. This effect is greater in the smoke chamber than in the reference chamber, and the imbalance causes the sensing electrode to become more positive.

The voltage at the sensing electrode is fed to a comparator where it is compared with a factory-set clean air reference voltage. If the monitored voltage exceeds the reference voltage, the comparator switches the alarm latch on, increasing the current drawn from the supply from about 40μA to a maximum of 75mA. This fall in the impedance of the detector is recognised by the control panel as an alarm signal.

The alarm latch current also illuminates the detector integral LED. A remote indicator connected between the L1 IN terminal and the –R terminal will have a voltage equal to the supply voltage less 1 volt across it and so will illuminate. See page 17 for details of the remote indicator.

To ensure correct operation of the detector the control panel must be arranged to supply a maximum of 33 volts DC and a minimum of 9 volts DC in normal operation.

The supply may fall to 6 volts DC in alarm conditions if a supply current of at least 10mA is available at this voltage. To ensure effective illumination of the integral LED and any remote indicator, the supply to the detector should exceed 12 volts.

To restore the detector to quiescent condition, it is necessary to expel any smoke and interrupt the electrical supply to the detector for a minimum of one second.